Reversible unit, air source for outdoor installation
44,9 - 211 kW
Outdoor unit for the production of chilled/hot water with two scroll compressors, optimized for low-GWP R454B refrigerant in a single-circuit configuration, axial-flow fans, condensing coil with copper tubes and aluminum fins and plate heat exchanger.
The new generation refrigerant R454B is the most eco-sustainable alternative to traditional refrigerant R410A, offering a 76% reduction in terms of GWP (Global Warming Potential GWP of R454B = 467, GWP of R410A = 1924 as per IPCC rev. 5th) and zero impact on the ozone layer.
WIDE OPERATING LIMITS
These units are operative at full load in heat pump mode down to -15°C outdoor air temperature, and up to 46°C in chiller mode without needing additional options. At -15°C outdoor air temperature, these heat pumps are able to produce hot water up to 42°C at full load.
ELECTRONIC EXPANSION VALVE
The use of the electronic expansion valve generates considerable benefits, especially in cases of variable demand and different external conditions. It has been introduced to these units as a result of accurate design choices concerning the cooling circuit and the optimization of operation in various different working conditions. The electronic expansion valve comes standard in the high-efficiency CA version.
CLASS A EFFICIENCY
The full range is also available with the Class A efficiency rating (in heating). CA version guarantees noise configurations at premium levels of efficiency thanks to the generous sizing of the refrigerant-exchange surface areas and to an accurate control of the fans.
TWO SOUND EMISSION LEVELS
Two different sound emission levels available. This means the best unit can be identified based on requirements, according to the system where it will be installed and the application.
INTEGRATED HYDRONIC GROUP
The optional built-in hydronic module already contains the main water circuit components; available with single or twin in-line, for achieving both low or high head.
Technical data
Technical data
Produkt-Informationen
Produkt-Informationen
K - Standard efficiency
LN-K - Low Noise, Key efficiency, and compact version
CA - Class A efficiency
LN-CA - Low Noise, Class A efficiency
- - Basic function
D - Partial condensing heat recovery function
Set-up for remote connectivity with ModBus/Echelon protocol cards
Remote control keyboard (distance 200m and 500m)
Traditional coils available with prepainted fins or Fin Guard Silver protective treatment.
Leak detector
Night mode to limit the maximum noise level of the unit.
User Limit Control (U.L.C.) allows for safe startup of the unit in critical water and air temperature conditions.
KIPlink user interface
Hydronic module with 1 or 2 pumps, high or low head. Buffer tank available.
Soft start
EC fans with DC brushless motor
Electronic control W3000+
W3000+ features an easy-to-use interface and a complete LCD display that allows one to consult and intervene by means of a multi-language menu (19 languages are available). The diagnostics includes a complete alarm management, with the “black-box” and the alarm history display for enhanced analysis of the unit operation. The programmable timer manages a weekly schedule organized into time bands to optimize unit performance by minimizing power consumption during periods of inactivity. Up to 10 daily time bands can be associated with different operating set points. As option, KIPlink is available - Keyboard In Your Pocket. KIPlink is the innovative user interface built on a web-based architecture, enabling direct interaction with the unit through a browser-based interface. The regulation features the continuous modulation of capacity, based on sequential adjustment + DIP referring to the leaving water temperature.
Optional proprietary devices can perform the adjustment of resources in systems made of several units. Consumption metering and performance measurement are possible as well. The variable primary flow control is always available as per standard (VPF.E function). Supervision can be easily developed via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet-over-IP, Bacnet MS/TP RS485, Konnex, ModBus TCP/IP, SNMP. Compatibility with the remote keyboard (up to 8 units).