NRCS-FC-Z 0152 - 1604

image
Air cooled chiller with free-cooling 50,6 - 542 kW
Outdoor unit for the production of chilled water, equipped with hermetic scroll compressors, R410A refrigerant, axial-fans, condensing coil with copper tubes and aluminum fins, braze-welded plate evaporator and thermostatic expansion valve. External panels are of peraluman, base of galvanized epoxy powder coated steel. The unit is supplied with anti-freeze oil and refrigerant and has been factory tested. On-site installation therefore just involves making connections to the mains power and water supplies. These chillers, fitted with free-cooling coils, are used when the cooling load is constant all-year-round or the outdoor air temperature is lower than the temperature of the liquid return line. In free cooling mode, the liquid is cooled by outdoor air, thus lowering the load of the compressors until it is reduced to zero. The NG configuration complies with applications where it is not allowed or desired the use of ethylene glycol.
EUROPE
CE
50 Hz

Product features

Features
FREE-COOLING
The generous size of the free-cooling coils allows to produce the nominal cooling capacity without the use of the compressors for many hours per year, thus cutting the annual energy consuption.
GROUP CONTROLS WITH DYNAMIC MASTER
Load sharing, sequencing, active redundancy, priority of resource activation, alarm management, theese are only some of the LAN functions that the unit is able to manage when connected to a group of chillers. Besides, the system's stability is ensured even in case of alarm or malfunctioning thanks to the Dynamic Master logic.
HPC
This function connects the indoor units (close control) with the external group of chillers. An advanced algorithm instantaneously detects the actual indoor thermal load and conveys this information to the chillers, thus optimizing the operation of the whole system.
ENERGY SAVINGS
Energy saving guaranteed by free-cooling, which exploits the low external air temperatures; free-cooling control with optional modulating valve.
INTEGRATED HYDRONIC GROUP
The built-in hydronic module already contains the main water circuit components; it is available with single or twin in-line pumps, to achieve both low or high head.
OUTSTANDING VERSATILITY
Units available in two different versions, B (basic) and SL (super low noise), in order to fully satisfy special requirements and comply with the most complex installation solutions.

Technical data

Technical data

Produkt-Informationen

Produkt-Informationen
  • B - Basic
  • SL - Super-low noise version
  • - - Basic function
  • NG - Function for free-cooling without the use of glycole
  • Multi Manager - LAN functions
  • HPC
  • EC fans with DC brushless motor
  • Modulating valve for water temperature control in Free-Cooling mode
  • Hydronic group
  • Automatic circuit breakers on loads
  • Set-up for remote connectivity with ModBus/Echelon protocol cards
  • Remote control keyboard (distance 200m and 500m)

Electronic control W3000+

W3000+ features an easy-to-use interface and a complete LCD display that allows one to consult and intervene by means of a multi-language menu (19 languages are available). The diagnostics includes a complete alarm management, with the “black-box” and the alarm history display for enhanced analysis of the unit operation. The programmable timer manages a weekly schedule organized into time bands to optimize unit performance by minimizing power consumption during periods of inactivity. Up to 10 daily time bands can be associated with different operating set points. As option, KIPlink is available - Keyboard In Your Pocket. KIPlink is the innovative user interface built on a web-based architecture, enabling direct interaction with the unit through a browser-based interface. The regulation features the continuous modulation of capacity, based on sequential adjustment + DIP referring to the leaving water temperature. Optional proprietary devices can perform the adjustment of resources in systems made of several units. Consumption metering and performance measurement are possible as well. The variable primary flow control is always available as per standard (VPF.E function). Supervision can be easily developed via proprietary devices or the integration in third party systems by means of the most common protocols as ModBus, Bacnet-over-IP, Bacnet MS/TP RS485, Konnex, ModBus TCP/IP, SNMP. Compatibility with the remote keyboard (up to 8 units).

Downloads

Downloads
Product brochures
Product brochures HPC EN
Product brochures RC FOR IT COOLING DE
Product brochures RC FOR IT COOLING EN
Informative data act
Informative data act RUT140 EN
Informative data act Applied Remote Suitcase EN
Informative data act W3000Touch+ EN
Informative data act Touch Room HMI EN
Informative data act KIPLink EN
Product overview
Product overview IT COOLING OVERVIEW - RC EN
Technical documentations - regulation (EU) N. 2016/2281
Technical documentations - regulation (EU) N. 2016/2281 NRCS-FC-Z 0152 - 1604 SEPR HT EN